Practical examples 91
Fault sequence, profile B
An example of the control sequence after a fault situation is described below.
Device is ready for restart.
Normal stop sequence, profile B
An example of the control sequence after a normal stop is described below.
Step Command
/ end state
Description 8.10 CCU STATUS WORD bits after command 7.01 MAIN
CONTROL
WORD
ISU RDYREF
MCB internal trip
MCB ON
Low voltage for ride through
remote
torque reduction
alarm
crowbar triggered
-
OFF 2 N STA
tripped
rdyref
rdyrun
rdyon
RESET
RUN
ON
b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b7 b3 b0
1 RUN=1 Device is running. 1 0 1 01000010111010
2 Device is tripped for any reason,
stator is immediately
disconnected from the grid and
after that ISU is disconnected
from the grid.
00001000011000010
3 RUN=0 Run command must be
removed.
00001000011000000
4 RESET=1Fault is reseted. 00001000010001100
5 RESET=0 RESET command must be
removed.
000
Step Command
/ end state
Description 8.10 CCU STATUS WORD bits after command 7.01 MAIN
CONTROL
WORD
ISU RDYREF
MCB internal trip
MCB ON
Low voltage for ride through
remote
torque reduction
alarm
crowbar triggered
-
OFF 2 N STA
tripped
rdyref
rdyrun
rdyon
RESET
RUN
ON
b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 b7 b3 b0
1 RUN=1 Device is running. 1 0 1 01000010111010
2 RUN=0 Device is requested to stop.
Stator current is controlled to
zero, stator is disconnected from
the grid and both INU and ISU
modulation is stopped and ISU is
disconnected from the grid.
00001000010011000
3 RUN=0 When speed is below SWITCH-
OFF speed.
00001000010001000