Fault tracing 417
A888 Edge counter 1
(Editable message text)
Programmable warning:
33.35 Edge counter 1 warn
message
Warning generated by
edge counter 1.
Check the source of the warning
(parameter 33.33 Edge counter 1
source).
A889 Edge counter 2
(Editable message text)
Programmable warning:
33.45 Edge counter 2 warn
message
Warning generated by
edge counter 2.
Check the source of the warning
(parameter 33.43 Edge counter 2
source).
A88A Value counter 1
(Editable message text)
Programmable warning:
33.55 Value counter 1 warn
message
Warning generated by
value counter 1.
Check the source of the warning
(parameter 33.53 Value counter 1
source).
A88B Value counter 2
(Editable message text)
Programmable warning:
33.65 Value counter 2 warn
message
Warning generated by
value counter 2.
Check the source of the warning
(parameter 33.63 Value counter 2
source).
A88C Device clean Warning generated by an
on-time timer.
Programmable warnings:
33.14 On-time 1 warn
message
33.24 On-time 2 warn
message
Check the auxiliary code. Check the
source of the warning corresponding
to the code:
0: 33.13 On-time 1 source
1: 33.23 On-time 2 source
10: 05.04 Fan on-time counter.
A88D DC capacitor
A88E Cabinet fan
A88F Cooling fan
A890 Additional cooling
A8A0 AI supervision
Programmable warning:
12.03 AI supervision function
An analog signal is
outside the limits
specified for the analog
input.
Check signal level at the analog input.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter group
12 Standard AI.
A8B0 Signal supervision
(Editable message text)
Programmable warning:
32.06 Supervision 1 action
Warning generated by a
signal supervision
function.
Check the source of the warning
(parameter 32.07, 32.17 or 32.28).
A8B1 Signal supervision 2
(Editable message text)
Programmable warning:
32.16 Supervision 2 action
Warning generated by
the signal supervision 2
function.
Check the source of the warning
(parameter 32.17 Supervision 2
signal).
A8B2 Signal supervision 3
(Editable message text)
Programmable warning:
32.26 Supervision 3 action
Warning generated by
the signal supervision 3
function.
Check the source of the warning
(parameter 32.27 Supervision 3
signal).
A8C0 Fan service counter A cooling fan has reached
the end of its estimated
lifetime. See parameters
05.41 and 05.42.
Check the auxiliary code. The code
indicates which fan is to be replaced.
0: Main cooling fan
1: Auxiliary cooling fan
2: Auxiliary cooling fan 2
3: Cabinet cooling fan
4: PCB compartment fan
Refer to the hardware manual of the
drive for fan replacement instructions.
Code
(hex)
Warning Cause What to do

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
Output currentUp to 5200 A
Input voltage380-690 V
Power range5600 kW
Cooling methodAir or liquid
Protection classIP21, IP54
Communication interfacesEthernet, CANopen

Related product manuals