116 Parameters
0…150% Main cooling fan age. 1 = 1%
05.42 Aux. fan service
counter
Displays the age of the auxiliary cooling fan as a
percentage of its estimated lifetime. The estimate is based
on the duty, operating conditions and other operating
parameters of the fan. When the counter reaches 100%, a
warning (A8C0 Fan service counter) is generated.
Can be reset from the control panel by keeping Reset
depressed for over 3 seconds.
-
0…150% Auxiliary cooling fan age. 1 = 1%
0000h...FFFFh Main control word. 1 = 1
06
06 Control and status
words
Drive control and status words.
06.01 Main control word The main control word of the drive. This parameter shows
the control signals as received from the selected sources
(such as digital inputs, the fieldbus interfaces and the
application program).
The bit assignments of the word are as described on
page 467. The related status word and state diagram are
presented on pages 468 respectively.
Note: Bits 12…15 can be used to carry additional control
data, and used as a signal source by any binary-source
selector parameter.
This parameter is read-only.
-
0000h...FFFFh Main control word. 1 = 1
06.02 Application control
word
The drive control word received from the application
program (if any). The bit assignments are described on
page 467.
This parameter is read-only.
-
0000h...FFFFh Application program control word. 1 = 1
06.03 FBA A transparent
control word
The unaltered control word received from the PLC through
fieldbus adapter A.
This parameter is read-only.
-
00000000h
…FFFFFFFFh
Control word received through fieldbus adapter A. -
06.04 FBA B transparent
control word
The unaltered control word received from the PLC through
fieldbus adapter B.
This parameter is read-only.
-
00000000h
…FFFFFFFFh
Control word received through fieldbus adapter B. 1 = 1
06.05 EFB transparent
control word
The unaltered control word received from the PLC through
the embedded fieldbus interface.
This parameter is read-only.
-
00000000h …
FFFFFFFFh
Control word received through the embedded fieldbus
interface.
1 = 1
No. Name/Value Description Def/
FbEq16