EasyManuals Logo
Home>ABB>DC Drives>ACS880 PCP

ABB ACS880 PCP User Manual

ABB ACS880 PCP
494 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background image
Standard programposi features 79
The following example shows the behavior of the motor potentiometer value.
Settings
Parameters 22.7122.80 (page 201).
DC voltage control
Overvoltage control
Overvoltage control of the intermediate DC link is typically needed when the motor is
in generating mode. To prevent the DC voltage from exceeding the overvoltage
control limit, the overvoltage controller automatically decreases the generating torque
when the limit is reached.
Undervoltage control
If the incoming supply voltage is cut off, the drive will continue to operate by utilizing
the kinetic energy of the rotating motor. The drive will be fully operational as long as
the motor rotates and generates energy to the drive. The drive can continue
operation after the break if the main contactor (if present) remained closed.
0
1
0
1
0
22.80
22.74
22.73
22.77
22.76
22.75

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS880 PCP and is the answer not in the manual?

ABB ACS880 PCP Specifications

General IconGeneral
BrandABB
ModelACS880 PCP
CategoryDC Drives
LanguageEnglish

Related product manuals