Parameters 303
SW 32bit Status Word (32 bits). 14
Act1 32bit Actual value ACT1 (32 bits). 15
Act2 32bit Actual value ACT2 (32 bits). 16
CW2 16bit Control Word 2 (16 bits).
When a 32-bit control word is used, this setting means the
most-significant 16 bits.
21
SW2 16bit Status Word 2 (16 bits).
When a 32-bit control word is used, this setting means the
most-significant 16 bits.
24
RO/DIO control word Parameter 10.99 RO/DIO control word.31
AO1 data storage Parameter 13.91 AO1 data storage.32
AO2 data storage Parameter 13.92 AO2 data storage.33
Feedback data
storage
Parameter 40.91 Feedback data storage. 40
Setpoint data storage Parameter 40.92 Setpoint data storage. 41
Other Source selection (see Terms and abbreviations on page
101).
-
58.102 Data I/O 2 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400002.
For the selections, see parameter 58.101 Data I/O 1.
Ref1 16bit
58.103 Data I/O 3 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400003.
For the selections, see parameter 58.101 Data I/O 1.
Ref2 16bit
58.104 Data I/O 4 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400004.
For the selections, see parameter 58.101 Data I/O 1.
SW 16bit
58.105 Data I/O 5 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400005.
For the selections, see parameter 58.101 Data I/O 1.
Act1 16bit
58.106 Data I/O 6 Defines the address in the drive which the Modbus master
accesses when it reads from or writes to register address
400006.
For the selections, see parameter 58.101 Data I/O 1.
Act2 16bit
58.107 Data I/O 7 Parameter selector for Modbus register address 400007.
For the selections, see parameter 58.101 Data I/O 1.
None
…… … …
58.124 Data I/O 24 Parameter selector for Modbus register address 400024.
For the selections, see parameter 58.101 Data I/O 1.
None
74
74 Pump setup
Basic functions of applications.
74.01 Pump enable Enables the pump functions related to parameters in
group 74 to 79.
Enable
Disable Disables pump function. 0
Enable Enables pump function. 1
No. Name/Value Description Def/
FbEq16