466 Fieldbus control through a fieldbus adapter
Scaling of references
The references are scaled as shown below. The values REFx MIN and REFx MAX
are set by parameters 46.01...46.07 which scaling is in use depends on the setting of
50.04 FBA A ref1 type and 50.05 FBA A ref2 type.
The scaled references are shown by parameters 03.05 FB A reference 1 and 03.06
FB A reference 2.
Actual values
Actual values are 16-bit words containing information on the operation of the drive.
The types of the monitored signals are selected by parameters 50.07 FBA A actual 1
type and 50.08 FBA A actual 2 type.
If parameter 50.12 FBA A debug mode is set to Fast, the actual values sent to the
fieldbus are displayed by 50.17 FBA A actual value 1 and 50.18 FBA A actual value
2.
REFx MAX
-(REFx MAX)
0
REF2: -10000
REF1: -20000
REF2: 10000
REF1: 20000
DriveFieldbus
0