Parameters 287
50.10 FBA A act1
transparent source
When parameter 50.07 FBA A actual 1 type is set to
Transparent or General this parameter selects the source
of actual value 1 transmitted to the fieldbus network
through fieldbus adapter A.
Not selected
Not selected No source selected. -
Other Source selection (see Terms and abbreviations on
page 101).
-
50.11 FBA A act2
transparent source
When parameter 50.08 FBA A actual 2 type is set to
Transparent or General this parameter selects the source
of actual value 2 transmitted to the fieldbus network
through fieldbus adapter A.
Not selected
Not selected No source selected. -
Other Source selection (see Terms and abbreviations on
page 101).
-
50.12 FBA A debug mode Enables the display of raw (unmodified) data received from
and sent to fieldbus adapter A in parameters
50.13…50.18.
This functionality should only be used for debugging.
Disable
Disable Display of raw data from fieldbus adapter A disabled. 0
Fast Display of raw data from fieldbus adapter A enabled. 1
50.13 FBA A control word Displays the raw (unmodified) control word sent by the
master (PLC) to fieldbus adapter A if debugging is enabled
by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h
…FFFFFFFFh
Control word sent by master to fieldbus adapter A. -
50.14 FBA A reference 1 Displays raw (unmodified) reference REF1 sent by the
master (PLC) to fieldbus adapter A if debugging is enabled
by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
…2147483647
Raw REF1 sent by master to fieldbus adapter A. -
50.15 FBA A reference 2 Displays raw (unmodified) reference REF2 sent by the
master (PLC) to fieldbus adapter A if debugging is enabled
by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
…2147483647
Raw REF2 sent by master to fieldbus adapter A. -
50.16 FBA A status word Displays the raw (unmodified) status word sent by fieldbus
adapter A to the master (PLC) if debugging is enabled by
parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
00000000h
…FFFFFFFFh
Status word sent by fieldbus adapter A to master. -
50.17 FBA A actual value 1 Displays raw (unmodified) actual value ACT1 sent by
fieldbus adapter A to the master (PLC) if debugging is
enabled by parameter 50.12 FBA A debug mode.
This parameter is read-only.
-
-2147483648
…2147483647
Raw ACT1 sent by fieldbus adapter A to master. -
No. Name/Value Description Def/
FbEq16