Programming
5-32
This group contains the necessary parameters to activate and program advanced features of the drive.
Feature
Select
Run On Power U
Parameter # 14 Factory Default ‘‘Disabled”
Parameter Type Read & Write
This parameter enables the function that allows the drive to
automaticall
restart on
ower u
re
ardless of what the
Units Text Settings ‘‘Enabled”
‘‘Disabled”
drive status was before power is lost. This applies only
when there is a maintained input to the start and stop
inputs. Refer to Chapter 2, Figure 2.7 through Figure 2.10.
ATTENTION: This parameter may only be used as
outlined in NFPA 79, paragraph 6-14 (exceptions 1-3)
for specialized applications. Equipment damage
and/or personal injury may result if this parameter is
used in an inappropriate application.
!
Reset/Run Tries
Parameter # 85 Factory Default 0
Parameter Type Read & Write Minimum 0
This value sets the maximum number of times the drive
attempts to reset a fault and restart before the drive issues
a ‘‘Max Retries Fault.” Not operative for faults 9, 10, 11,
24, 25, 26, 29, 30, 32, 33, 34, 35, 38, 39, 40, 41, 42,
43 and 48.
Important: [Reset/Run Tries] is a cumulative count. This
counter resets to zero if four (4) minutes elapses since the
last fault.
Units Numeric Maximum 9