EasyManuals Logo
Home>Allen-Bradley>Controller>1305 Series

Allen-Bradley 1305 Series User Manual

Allen-Bradley 1305 Series
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
Installation/Wiring
2-16
Table 2.E Maximum Motor Cable Length
Reactor
at the Drive With 1204-TFB2 Terminator With 1204-TFA1 Terminator
Using a Motor with Insulation V
P-P
Usin
a Motor with Insulation V
-
Using a Motor with Insulation V
P-P
Drive HP Motor HP
1000 Volt 1200 Volt or 1600 Volt
-
1000 Volt or 1200 Volt
1000 Volt 1200 Volt
Drive
HP
(460V)
Motor
HP
(460V)
Any Cable Shielded Unshielded Shielded Unshielded Shielded Unshielded Shielded Unshielded
Maximum Carrier Frequency 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz 2 kHz
High-Line Derating Multiplier 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
5 5 15m (50ft) 182m (600ft) 182m (600ft) NR NR 91m (300ft) 61m (200ft) 91m (300ft) 121m (400ft)
3 15m (50ft) 182m (600ft) 182m (600ft) 91m (300ft) 121m (400ft) 99m (325ft) 61m (200ft) 152m (500ft) 121m (400ft)
2 15m (50ft) 182m (600ft) 182m (600ft) 121m (400ft) 182m (600ft) 99m (325ft) 61m (200ft) 182m (600ft) 121m (400ft)
3 3 15m (50ft) 91m (300ft) 182m (600ft) NR NR 91m (300ft) 61m (200ft) 91m (300ft) 121m (400ft)
2 15m (50ft) 182m (600ft) 182m (600ft) 91m (300ft) 121m (400ft) 99m (325ft) 61m (200ft) 152m (500ft) 121m (400ft)
1 15m (50ft) 182m (600ft) 182m (600ft) 91m (300ft) 182m (600ft) 99m (325ft) 61m (200ft) 182m (600ft) 121m (400ft)
2 2 15m (50ft) 76m (250ft) 167m (550ft) NR NR 91m (300ft) 61m (200ft) 91m (300ft) 121m (400ft)
1 15m (50ft) 182m (600ft) 182m (600ft) 61m (200ft) 61m (200ft) 99m (325ft) 61m (200ft) 121m (400ft) 121m (400ft)
0.5 15m (50ft) 182m (600ft) 182m (600ft) 91m (300ft) 121m (400ft) 99m (325ft) 61m (200ft) 152m (500ft) 121m (400ft)
1 1 15m (50ft) 68m (225ft) 152m (500ft) NR NR 45m (150ft) 61m (200ft) 45m (150ft) 76m (250ft)
0.5 15m (50ft) 121m (400ft) 182m (600ft) NR NR 76m (250ft) 61m (200ft) 76m (250ft) 121m (400ft)
0.5 0.5 15m (50ft) 45m (150ft) 106m (350ft) NR NR NR NR NR NR
NR = Not Recommended.
Important: A 3% reactor reduces motor stress but may cause a degradation of motor waveform quality. Reactors must have a turn-to-turn insulating rating of 2100 volts or higher.
Reactors are not recommended for lightly loaded applications because overvoltage trips may result at low output frequencies.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1305 Series and is the answer not in the manual?

Allen-Bradley 1305 Series Specifications

General IconGeneral
BrandAllen-Bradley
Model1305 Series
CategoryController
LanguageEnglish

Related product manuals