Programming
5-48
Masks Group (continued)
Start Mask
Parameter # 95 Factory Default 01111111
Parameter Type Read & Write
This parameter determines which adapters can issue start
commands.
Units Byte Settings 1
0
Permit Control
Deny Control
Jo
Mask
Parameter # 96 Factory Default 01111111
Parameter Type Read & Write
This parameter determines which adapters can issue jog
commands.
Units Byte Settings 1
0
Permit Control
Deny Control
Reference Mask
Parameter # 97 Factory Default 01111111
Parameter Type Read & Write
This parameter determines which adapters can control the
switching between the available freq. reference sources.
Important: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control
Accel Mask
Parameter # 98 Factory Default 01111111
Parameter Type Read & Write
This parameter determines which adapters can switch
between [Accel Time 1] and [Accel Time 2].
Important: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control
Decel Mask
Parameter # 99 Factory Default 01111111
Parameter Type Read & Write
This parameter determines which adapters can switch
between [Decel Time 1] and [Decel Time 2].
Important: Terminal Block (TB2) will have control unless
masked out.
Units Byte Settings 1
0
Permit Control
Deny Control