Programming
5-51
Owners Group (continued)
[Start Owner]
Parameter # 104
Parameter Type Read Only
This parameter displays which adapters are currently
issuing Start commands. Since Start commands are edge
triggered, multiple adapters can issue the Start command
simultaneously and as such are displayed. However, it is
the first low to high transition of the Start (once all Stops
and/or Faults are removed) that initiates the actual Start
command.
Units Byte Settings 1
0
Controlling
Not Controlling
[Jo
Owner]
Parameter # 105
Parameter Type Read Only
This parameter displays which adapters are currently
issuing Jog commands. Since the Jog function is
momentary, multiple adapters can issue Jog commands
simultaneously. This means that all adapters issuing the
Jog must stop commanding the Jog before the function
ceases.
Important: Stop commands will terminate Jog control and
Start commands will override any Jog command.
Units Byte Settings 1
0
Controlling
Not Controlling