Programming
5-36
Feature Select Group (continued)
[
Sli
p
Com
p
Adder
]
Parameter # 148 Factory Default None
[Slip
Comp
Adder]
Parameter Type Read Only Minimum 0.00 Hz
Displays the frequency added to the drive output due to the
slip compensation feature. See [Rated Slip] for additional
information.
Units 0.01 Hz Maximum 5.00 Hz
[IR Comp %]
Parameter #
PtT
147
Read & Write
Factory Default
Mi i
See Table
0%
0.37 kW
(0.5 HP)
0.55 kW
(0.75 HP)
0.75 kW
(1 HP)
1.5 kW
(2 HP)
2.2 kW
(3 HP)
4.0 kW
(5 HP)
Parameter Type
Read & Write
Minimum 0%
230V 45% 45% 45% 45% 45% N/A
A voltage is added to the output based on torque Units 1% Maximum 150%
460V 75% 75% 75% 60% 50% 50%
A
voltage
is
added
to
the
output
based
on
torque
current. An additional 31 volts (maximum) is added
to 460 volt units to compensate for stator
resistance. 15.5 volts is added for 230 volt units. If
the drive trips on an Overload fault (F7), or has
trouble accelerating to commanded speed, this
value should be reduced. A setting of 0% disables
this function.
Units
1%
Maximum
150%
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1305 Series and is the answer not in the manual?

Allen-Bradley 1305 Series Specifications

General IconGeneral
BrandAllen-Bradley
Model1305 Series
CategoryController
LanguageEnglish

Related product manuals