Rockwell Automation Publication 1734-UM013N-EN-P - September 2017 215
Appendix F
I/O Assemblies
Input Assemblies
Topic Page
Input Assemblies 215
Output Assemblies 216
Analog Input Assemblies 216
Configuration Assemblies 219
Using Data from Modules Configured Via the Generic Profile 225
Table 26 - 1734-IB8S Input Assemblies
Instance
Decimal
(hex)
Connection
Type
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
516 (204 h) Safety and
Standard
0 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
548 (224 h) Safety Only 0 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1 Safety Input 7
Status
Safety Input
6 Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
768 (300 h) Standard Only 0 Reserved Input Power
Error
788 (314 h) Safety and
Standard
0 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1Combined
Safety Input
Status
Reserved Input Power
Error
(1)
Reserved Reserved Reserved Muting Lamp 3
Status
Muting Lamp 1
Status
820 (334 h) Safety and
Standard
0 Safety Input
7
Safety Input
6
Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1 Safety Input
7 Status
Safety Input
6 Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
2ReservedInput Power
Error
(1)
Reserved Muting Lamp 3
Status
Muting Lamp 1
Status
868 (364 h) Safety and
Standard
0 Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0
1 Safety Input
7 Status
Safety Input
6 Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
2 Reserved Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
3ReservedInput Power
Error
(1)
Reserved Muting Lamp 3
Status
Muting Lamp
1Status
899 (383 h) Standard 0 Reserved Input Power
Error
1 Reserved Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
(1) This data is diagnostic only and does not have safety integrity.