Programming and Parameters 3-15
Terminal Block Group (continued)
T056 [Relay Out1 Level] Related Parameter(s): T055, T058, T059, d318
32 bit parameter.
Sets the trip point for the digital output relay if the value of T055
[Relay Out1 Sel] is 6, 7, 8, 9, 10 or 12.
Values Default: 0.0
Min/Max: 0.0/9999
Display: 0.1
32
T055 Setting T056 Min/Max
6
7
8
9
10
12
0/320 Hz
0/180%
0/815 Volts
0/100%
1/180 degs
0/1
T058 [Relay 1 On Time] Related Parameter(s): T055, T056, T059
Sets delay time before Relay energizes after required condition testing.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
T059 [Relay 1 Off Time] Related Parameter(s): T055, T056, T058
Sets delay time before Relay de-energizes after required condition testing ceases.
Important: Do not use this parameter with Auxiliary Motor Control mode AutoSwap enabled.
Values Default: 0.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs