Programming and Parameters 3-23
Terminal Block Group (continued)
T077 [Sleep-Wake Sel] Related Parameter(s): T078, T079, T080, T081
The drive “sleeps” if the appropriate analog input drops below the set [Sleep Level] for the time set in
[Sleep Time] and the drive is running. When entering sleep mode the drive will ramp to zero and the
run indicator ( ) on the keypad display will flash indicating the drive is in “sleep” mode.
When the appropriate analog input rises above the set [Sleep Level] the drive will “wake” and ramp to
the commanded frequency.
Inversion can be accomplished by setting T078 [Sleep Level] to a higher setting than T080 [Wake
Level].
Options 0 “Disabled” (Default)
1 “Analog In 1” Sleep enabled from Analog Input 1.
2 “Analog In 2” Sleep enabled from Analog Input 2.
3 “Command Freq” Sleep enabled based on drive commanded frequency.
!
ATTENTION: Enabling the Sleep-Wake function can cause unexpected machine
operation during the Wake mode. Equipment damage and/or personal injury can result if
this parameter is used in an inappropriate application. In addition, all applicable local,
national & international codes, standards, regulations or industry guidelines must be
considered.
T078 [Sleep Level] Related Parameter(s): T077, T079, T080, T081
Sets the analog input level the drive must reach to enter sleep mode.
Values Default: 10.0%
Min/Max: 0.0/ 100.0%
Display: 0.1%
T079 [Sleep Time] Related Parameter(s): T077, T078, T080, T081
Sets the analog input time the drive must stay below to enter sleep mode.
Values Default: 0.0 Secs
Min/Max: 0.0/ 600.0 Secs
Display: 0.1 Secs
T080 [Wake Level] Related Parameter(s): T077, T078, T079, T081
Sets the analog input level the drive must reach to wake from sleep mode.
Values Default: 15.0%
Min/Max: 0.0/ 100.0%
Display: 0.1%
T081 [Wake Time] Related Parameter(s): T077, T078, T079, T080
Sets the analog input time the drive must stay above to wake from sleep mode.
Values Default: 0.0 Secs
Min/Max: 0.0/ 600.0 Secs
Display: 0.1 Secs

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex400 and is the answer not in the manual?

Allen-Bradley PowerFlex400 Specifications

General IconGeneral
EnclosureNEMA/UL Type 4/4X
Control MethodVolts per Hertz, Sensorless Vector Control
CommunicationRS485
Output Voltage0 to Input Voltage
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Storage Temperature-40°C to 70°C (-40°F to 158 °F)
Humidity5...95% noncondensing
AltitudeUp to 1000m (3280ft) without derating
Input Voltage200-240VAC, 380-480VAC, 500-600VAC, 600-690VAC (depending on model)

Summary

Important User Information

Safety Definitions

Defines safety terms like Warning, Attention, Shock Hazard, and Burn Hazard.

Overview

General Precautions

Covers critical safety warnings regarding voltage, ESD, and installation errors.

Chapter 1 Installation/Wiring

Opening the Cover

Provides instructions on how to open the drive cover for Frame C.

Mounting Considerations

Specifies mounting orientation, surface requirements, temperature, and clearances.

AC Supply Source Considerations

Explains considerations for ungrounded distribution systems and MOV disconnection.

General Grounding Requirements

Details safety ground, motor ground, and shield termination requirements.

Fuses and Circuit Breakers

Recommends fuse ratings and circuit breakers for branch circuit protection.

Power Wiring

Lists acceptable motor cable types and installation guidelines, including shock hazard warnings.

I/O Wiring Recommendations

Provides recommendations and precautions for control and signal wiring.

Start and Speed Reference Control

Explains various methods for controlling the drive's start and speed reference.

Chapter 2 Start Up

Before Applying Power to the Drive

Lists essential checks before applying power, including safety precautions.

Integral Keypad Operation

Describes the operator keys, LED indicators, and LCD display functions.

Chapter 3 Programming and Parameters

About Parameters

Explains the types of parameters: ENUM, Numeric, and Bit.

Parameter Organization

Details the organization of parameters into groups like Basic Display and Program.

Basic Program Group

Details core parameters for motor configuration and basic operation.

Terminal Block Group

Explains parameters related to digital and analog inputs/outputs and relay functions.

Advanced Program Group

Details advanced parameters for PID, AutoSwap, and other specialized functions.

Chapter 4 Troubleshooting

Faults

Defines faults and categorizes them into Auto-Reset/Run and Non-Resetable types.

Table 4.A Fault Types, Descriptions and Actions

Lists common faults, their descriptions, and corrective actions.

Common Symptoms and Corrective Actions

Provides guidance for diagnosing and resolving common drive issues like no start or unstable operation.

Appendix A Supplemental Drive Information

Specifications

Details electrical, control, and input/output specifications for the drive.

Environment

Covers environmental operating conditions including temperature and atmosphere.

Appendix B Accessories and Dimensions

Table B.2 PowerFlex 400 Drives

Lists drive ratings, output current, catalog numbers, and frame sizes.

Product Dimensions

Provides weight information for PowerFlex 400 frames.

Appendix C RJ45 DSI Splitter Cable

Connectivity Guidelines

Provides guidelines for connecting peripherals using the RJ45 DSI Splitter Cable.

Appendix D Application Notes

Damper Control Setup

Explains how to embed damper control logic within the drive for cost reduction.

PID Setup

Explains the PID control loop and how to enable it for process control.

Appendix E Modbus RTU Protocol

Parameter Configuration

Lists PowerFlex 400 parameters used for configuring the drive on a network.

Appendix F Metasys N2

Using Metasys Configurable Objects to Access Parameters

Details reading and writing parameter values via configurable objects.

Appendix G P1 – Floor Level Network (FLN)

Network Points

Lists the point database for Application 2735, mapping points to parameters.

Using P1 Configurable Points to Access Parameters

Explains reading and writing parameter values using P1 configurable points.

Related product manuals