EasyManuals Logo
Home>Allen-Bradley>Controller>PowerFlex400

Allen-Bradley PowerFlex400 User Manual

Allen-Bradley PowerFlex400
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
1-20 Installation/Wiring
I/O Wiring Examples
Input/Output Connection Example Required Settings
Potentiometer
1-10k Ohm Potentiometer
Recommended
(2 Watt Minimum)
DIP Switch
AI1 = 10V
Parameters
P038 [Speed Reference] = 2 “Analog In1”
T069 [Analog In 1 Sel] = 2 “0-10V”
Scaling
T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]
Check Results
d305 [Analog In 1]
Analog Input
Bipolar Speed Reference,
±10V Input
DIP Switch
AI2 = 10V
Parameters
P038 [Speed Reference] = 3 “Analog In2”
T073 [Analog In 2 Sel] = 3 “-10 to +10V”
Scaling
T074 [Analog In 2 Lo]
T075 [Analog In 2 Hi]
Check Results
d306 [Analog In 2]
Analog Input
Unipolar Speed Reference,
0 to +10V Input
DIP Switch
AI1 = 10V
Parameters
P038 [Speed Reference] = 2 “Analog In1”
T069 [Analog In 1 Sel] = 2 “0-10V”
Scaling
T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]
Check Results
d305 [Analog In 1]
Analog Input
Unipolar Speed Reference,
4-20 mA Input
DIP Switch
AI1 = 20MA
Parameters
P038 [Speed Reference] = 2 “Analog In1”
T069 [Analog In 1 Sel] = 1 “4-20 mA”
Scaling
T070 [Analog In 1 Lo]
T071 [Analog In 1 Hi]
Check Results
d305 [Analog In 1]
Analog Output
Unipolar, 0 to +10V Output
1k Ohm Minimum
DIP Switch
AO1 = 10V
Parameters
T082 [Analog Out1 Sel] = 0 through 6
Scaling
T083 [Analog Out1 High]
T084 [Analog Out1 Setpt]
12
13
14
17
18
-/+ 10V
Common
13
14
+
Common
13
14
+
Common
14
15
Common
+

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex400 and is the answer not in the manual?

Allen-Bradley PowerFlex400 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex400
CategoryController
LanguageEnglish

Related product manuals