Chapter 3: Configuration and commissioning
54 2X Series Installation Manual
Configures the control panel date and time, and to synchronize the
date and time in a fire network. See “Date and time” on page 40.
Night mode Configures the sensitivity settings for the day/night schedule and
for the holiday calendar. See “Day/night mode sensitivity settings”
on page 41.
Configures the control panel's regional operation mode.
Configures the control panel fire network.
s Configures TCP/IP communication settings, to manage email
accounts (for event notifications), and to safely remove a USB
device.
Configures general panel settings, including 24V AUX output, fault
mask, sounder re-sound, school bell settings, etc.
onfiguration Loads a new configuration, saves the current configuration file to a
USB flash drive, restores the previous configuration, or restores
default factory settings.
Configures any installed expansion boards.
Loads auxiliary files from a USB flash drive. Auxiliary files that can
be loaded include custom standby and alarm screens,
language or font files for extended language support.
Loads control panel firmware updates.
Configures external and internal printer settings.
Configures Ethernet, central monitoring station, PSTN, and GPRS
settings for an installed DACT board.
ID configuration
Select the ID configuration option to configure the control panel Firenet ID (for
the fire network) and description. The ID must be in the range 01 to 32. The
default ID is 01.
To change the ID or description:
1. Select Panel setup from the Main menu.
2. Select ID configuration.
3. Enter the ID and description.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.