Probe unit (functionality)
Function description66
Version: 1.5
The following window (left) appears for a configuration with „Refer-
ence signal feedback“ .
• Confirm with OK
The "Feedback 1" menu appears.
• Select the source of the "Feedback reference
signal" (usually „Zero index“).
Further settings are required in the "Probe unit" window (left).
• Press the „Logic“ button.
The trigger signal can be linked to a further signal source (Mux 2).
The simplest case consists of a signal source and the combination
logic ("logic operation").
• Specify which signal edge (positive or negative) should be
evaluated in the signal sequence (Pos Edge or Neg Edge).
• The decision for a particular signal edge is made during
parameterization of the AX5000 servo drive. It is not
possible to select it later in the control program (NC / CNC).
In the last step the "Mode" and the activation type are specified.
Mode probe 1: 0 Single measuring:
After each measurement event the new process must be activated
through a
0-1 enable switch (default).
Mode probe 1: 1 Continuous measuring:
The measurement is repeated as long as enable remains 1.
Auto activation: 0:Activation with S-0-0170:
The probe unit is activated with command S-0-0170 from the user
program (default).
Auto activation 1: Auto activation from SafeOp to Op:
The probe unit is enabled automatically when the AX5000 switches
from SafeOp state to Op.
Once all options have been selected, press "Modify settings in startup list and process data". An overview appears, which lists the pa-
rameters and process data to be modified. Confirm with OK. If the AX5000 is properly linked to an NC axis, the settings required for this
axis are implemented automatically.