â–„ ASR 5000 Installation Guide
Periodic Status Checks
Depending upon system usage and performance, you may want to perform these tasks more frequently than
recommended.
Table 81. Periodic Status Checks
Check for unused or unneeded file on the CompactFlash.
Delete unused or unneeded files to conserve space using the delete
command. You should also perform the next action in list. See Note
below.
Synchronize the contents of the CompactFlash on both SMCs to ensure
consistency between the two (Exec mode command).
filesystem synchronize all
Generate a crash list (and other show command information) and save
the output as a tar file.
show support details <to location and
filename>
Flash: [file: ]{ /flash | /pcmcia1 | /hd }[ /directory
]/file_name
TFTP: tftp://{ host[ :port# ] }[ /directory
]/file_name
SFTP: [ ftp: | sftp: ]//[ username[ :password ]@ ]
{ host }[ :port# ][ /directory ]/file_name
NOTE: If there is an issue with space, you can remove alarm and crash information from the system; however, this practice is
not recommended. Support and engineering personnel use these records for troubleshooting if a problem should develop. You
should request assigned support personnel to remove these files after storing the information for possible future use.
View a listing of all cards installed in the chassis with hardware revision,
part, serial, assembly, and fabrication numbers.
show hardware card
show hardware inventory
show hardware system
View all cards installed in the chassis with hardware revision, and the
firmware version of the on-board Field Programmable Gate Array
(FPGAs).
show hardware version board
You should replace the particulate air filter installed directly above the lower fan tray in the chassis. Refer to the Replacing the
Chassis Air Filter section of this guide for detailed instructions.