ID-FLX Lite & Telecom Global Guide
112
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 2 -
Step 1
Comm object 8394 Related applications
Description
Time of the PRESTART output closed prior to the engine start – i.e. before the binary outputs Fuel solenoid
and Starter are closed and opens when Starting RPM speed is reached. Set to zero if you want to leave the
output PRESTART opened.
Prestart time
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] 0 .. 600 [s]
Default value 0 -
Step 1
Comm object 11836 Related applications N/A
Description
This setpoint is used for setting of timer for deactivation of GLOW PLUGS (PAGE 216).
Preglow time
6 back to List of setpoints
Setpoint group Engine parameters Related FW 2.5.0
Range [units] -600 .. PreheatTemp2 (page 113)[°C]
Default value 0 °C -
Step 1 °C
Comm object 15985 Related applications N/A
Description
Defines the temperature, at which the LBO Preheat activate of the longest time prior to engine start. See
description of PREHEAT (PAGE 198).
PreheatTemp1
6 back to List of setpoints