ID-FLX Lite & Telecom Global Guide
140
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100.0 .. +1000.0 [Bar]
Default value 2.0 -
Step 0.1
Comm object 8369 Related applications
Description
Warning limit level for ANALOG INPUT 1.
AIN1 Level 1
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100.0 .. +1000.0 [Bar]
Default value 1.0 -
Step 0.1
Comm object 8370 Related applications
Description
Shutdown limit level for ANALOG INPUT 1.
AIN1 Level 2
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 180 [s]
Default value 3 -
Step 1
Comm object 8365 Related applications
Description
Delay for ANALOG INPUT 1.
Note: Analog input 1 is usually determined to Oil Pressure measurement and it is resistive type of input
with range 0-2500 Ω.
AIN1 Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100 .. 10000 [°C]
Default value 80 -
Step 1
Comm object 8375 Related applications
Description
Warning limit level for ANALOG INPUT 2.
AIN2 Level 1
6 back to List of setpoints