EasyManuals Logo
Home>ComAp>Controller>InteliDrive Lite

ComAp InteliDrive Lite Global Guide

ComAp InteliDrive Lite
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #140 background imageLoading...
Page #140 background image
ID-FLX Lite & Telecom Global Guide
140
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100.0 .. +1000.0 [Bar]
Default value 2.0 -
Step 0.1
Comm object 8369 Related applications
Description
Warning limit level for ANALOG INPUT 1.
AIN1 Level 1
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100.0 .. +1000.0 [Bar]
Default value 1.0 -
Step 0.1
Comm object 8370 Related applications
Description
Shutdown limit level for ANALOG INPUT 1.
AIN1 Level 2
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 180 [s]
Default value 3 -
Step 1
Comm object 8365 Related applications
Description
Delay for ANALOG INPUT 1.
Note: Analog input 1 is usually determined to Oil Pressure measurement and it is resistive type of input
with range 0-2500 Ω.
AIN1 Del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] -100 .. 10000 [°C]
Default value 80 -
Step 1
Comm object 8375 Related applications
Description
Warning limit level for ANALOG INPUT 2.
AIN2 Level 1
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals