ID-FLX Lite & Telecom Global Guide
197
Related FW 2.5.0 Related applications
Comm object 24
Description
Closed relay energizes the starter of engine.
The relay opens if:
The strating speed is reached or
Maximum time of cranking is exceeded or
Request to stop comes up
Starter
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 22
Description
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
Emergency stop comes or
Cooled engine is stopped or
In pause between repeated starts
Fuel solenoid
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 23
Description
The closed output energizes stop solenoid to stop the engine.
The output is active at least for Stop time, if the stop lasts longer; it stays active until all symptoms say the
engine is stopped.
The engine is stopped if:
RPM < 2 and
Oil pressure < Starting POil (page 111)
Note: The engine can be started anytime, if all symptoms say the engine is steady regardless of the fact
the Stop solenoid can still be active (in that case it is deactivated before cranking).
Note: In case when stop time period is lower than "stop engine detected" + 10s, stop time period is
extended to this value due to safety reason. (stop engine detected = RPM<2, OilP not detected, D+ not
active)
Stop solenoid