EasyManuals Logo
Home>ComAp>Controller>InteliDrive Lite

ComAp InteliDrive Lite Global Guide

ComAp InteliDrive Lite
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
ID-FLX Lite & Telecom Global Guide
73
6.1.4 Shut down (Sd)
When the shutdown alarm comes up, ID-Lite opens all outputs e.g. FUEL SOLENOID, STARTER and
PRESTART to stop the engine immediately. Alarm outputs and common shutdown output are closed. Active or
not reset protection disables start.
Note: Engine running only alarms are activated after Eng prot del (page 136) , after the engine RPM >
Starting RPM (page 111) during the engine starting procedure.
Note: If SPRINKLER (PAGE 186) is active engine does not react on shutdown protection only for Emergency
stop and Overspeed protection.
Sensor fail Fls is detected when measured value is 6% out of range. Controller screen displays in this case
string #### instead measured value.
Note: For list of possible shut-down alarms see List of possible alarms on page 73.
6.1.5 List of possible alarms
Events
specification
Protection
type
Information on binary
output available
(see List of LBO on page
195)
Description
Wrn Oil Press WRN YES
Oil pressure is smaller than Wrn Oil
press setpoint.
Sd Oil Press SD YES
Oil pressure is smaller than Sd Oil
press setpoint.
Sd NotOilPress SD YES
No information about the oil
pressure from the binary oil pressure
sensor.
WrnEngineTemp WRN YES
Water temperature is greater than
Wrn Water temp setpoint.
Sd Engine Temp SD YES
Water temperature is greater than
Sd Water temp setpoint.
Wrn Fuel Level WRN YES
Fuel level is smaller than Wrn Fuel
Level setpoint.
Sd Fuel Level SD YES
Fuel level is smaller than Sd Fuel
Level setpoint.
Ubat WRN YES
Battery voltage is out of limits given
by Batt overvolt and Batt undervolt
setpoints.
Wrn AIN WRN YES
Warning alarm configurable on the
input of the controller.
Sd AIN SD YES
Shutdown alarm configurable on the
input of the controller.
Wrn AIO WRN YES
Warning alarm configurable on the
input of plug-in.

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals