ID-FLX Lite & Telecom Global Guide
203
Related FW 2.5.0 Related applications
Comm object 1296
Description
Output closes if the engine “Sd Underspeed” alarm activates i.e. when RPM is below the Starting RPM
(page 111) limit.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Underspeed
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 1291
Description
Output closes after the engine start-up fails.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Start failed
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 1292
Description
Output closes when ID-Lite performs reset during start procedure (probably due to weak battery).
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Battery flat
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 928
Description
Output closes when battery over/under voltage warning appears.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
V batt failed
6 back to List of LBO