ID-FLX Lite & Telecom Global Guide
201
Related FW 2.5.0 Related applications
Comm object 62
Description
The output is closed if following conditions are fulfilled:
Engine is not running and
No Shut down or Slow stop alarm is active
Controller is not in OFF mode
Ready
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 58
Description
The output is closed if engine is running and no alarm is active – it is possible to close load. The output opens
when Wrn Underspeed protection is active and during cooling state.
Ready to load
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 67
Description
Output closes if the engine is in Running state.
Running
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 74
Description
The output closes when engine is in Cooling state.
Cooling
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 592
Description
One second pulse as echo for panel Fault reset button.
Fault Reset
6 back to List of LBO