EasyManuals Logo
Home>ComAp>Controller>InteliDrive Lite

ComAp InteliDrive Lite Global Guide

ComAp InteliDrive Lite
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
ID-FLX Lite & Telecom Global Guide
130
Setpoint group Load limit Related FW 2.5.0
Range [units]
CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7, CU:AI8, CU:AI9,
AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4, RPM-BI3 [-]
Default value CU:AI1 YES
Step -
Comm object 11839 Related applications
Description
This is comparator with hysteresis analog input selection from controller analog inputs or from extension
module inputs. It is also possible to use Binary input 3 in function of RPM detection.
Reg CMP Input
6 back to List of setpoints
Setpoint group Load limit Related FW 2.5.0
Range [units] -10000 .. +10000 [-]
Default value 0 YES
Step 1
Comm object 11841 Related applications
Description
Limit to close SPEEDSWITCH (PAGE 217).
Value of this Setpoint should be given in value of quantity without decimal point.
Example: When AIN is configured in such way that Load limit set on 5V to maintain the value
8.54bar, then the value inserted to this Setpoint is 854.
Reg CMP On
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals