Output freq.STW
Follower-master
e30ba273.11
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit
no.:
Figure 66: Status Word
Table 56: Status Word According to FC Profile
Bit Bit = 0 Bit = 1
00 Control not ready Control ready
01 Drive not ready Drive ready
02 Coasting Enable
03 No error Trip
04 No error Error (no trip)
05 Reserved
06 No error Triplock
07 No warning Warning
08 Speed≠reference Speed=reference
09 Local operation Bus control
10 Out of frequency limit Frequency limit OK
11 No operation In operation
12 Drive OK Stopped, auto start
13 Voltage OK Voltage exceeded
14 Torque OK Torque exceeded
15 Timer OK Timer exceeded
6.1.8.4 Explanation of Status Word Bit
Bit 00, Control Not Ready/Ready
Bit 00=0: The drive trips.
Bit 00=1: The drive controls are ready but the power component does not necessarily receive any supply (if there is 24 V external supply
to controls).
Bit 01, Drive Ready
Bit 01=0: The drive is not ready.
Bit 01=1: The drive is ready for operation, but the coasting command is active via the digital inputs or via serial communication.
Bit 02, Coast Stop
Bit 02=0: The drive releases the motor.
100 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss iC2 and is the answer not in the manual?

Danfoss iC2 Specifications

General IconGeneral
BrandDanfoss
ModeliC2
CategoryMedia Converter
LanguageEnglish

Related product manuals