Application Guide | iC2-Micro Frequency Converters
7.5 Motor (Menu Index 4)
7.5.1 Status (Menu Index 4.1)
P 4.1.1 Motor Current
View the motor current measured as a mean value, Irms.
Default value: 0.00 Parameter type: Range (0.00–655.35)
Parameter
number:
1614 Unit: A
Data type: uint16 Access type: Read
P 4.1.2 Motor Voltage
View the motor voltage, a calculated value used for controlling the motor.
Default value: 0 Parameter type: Range (0–65535)
Parameter
number:
1612 Unit: V
Data type: uint32 Access type: Read
P 4.1.3 Motor Electrical Power
Motor power consumption in kW. The value shown is calculated on basis of the actual DC-link voltage and DC-link current.
Default value: 0.000 Parameter type: Range (0.000–1000.000)
Parameter
number:
1610 Unit: kW
Data type: uint32 Access type: Read
P 4.1.4 Motor Power Hp
Motor power consumption in kW. The value shown is calculated on basis of the actual DC-link voltage and DC-link current.
Default value: 0.000 Parameter type: Range (0.000–1000.000)
Parameter
number:
1611 Unit: Hp
Data type: uint32 Access type: Read
P 4.1.5 Motor Thermal Load
View the calculated motor temperature in percentage of allowed maximum. At 100% a trip will occur, if the ETR function selected in P
4.6.7 Motor Thermal Protection.
Default value: 0 Parameter type: Range (0–100)
Parameter
number:
1618 Unit: %
Data type: uint8 Access type: Read
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 121