Selection number Selection name Selection description
0 Normal The motor shaft turns in clockwise direction when frequency
converter is connected U⇒U; V⇒V; and W⇒W to motor.
1 Inverse The motor shaft turns in counterclockwise direction when
frequency converter is connected U⇒U; V⇒V; and W⇒W to
motor.
P 4.4.1.5 Motor Control Bandwidth
Select type of motor control bandwidth.
Default value: 1 [Medium] Parameter type: Selection
Parameter
number:
108 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 High For high dynamic response.
1 Medium Optimized for smooth steady state operation.
2 Low Optimized for smooth steady state operation with lowest
dynamic response.
3 Adaptive 1 Optimized for smooth steady state operation, with extra active
damping.
4 Adaptive 2 Focuses on low-inductance PM motors. This option is an
alternative to [3] Adaptive 1.
7.5.3.2 AC-Brake (Menu Index 4.4.2)
P 4.4.2.1 Enable AC Brake
Select the method for dissipation of excess brake energy.
Default value: 0 [Disable] Parameter type: Selection
Parameter
number:
210 Unit: –
Data type: enum Access type: Read/Write
Selection number Selection name
0 Disable
1 Enable
P 4.4.2.2 AC Brake, Max current