Application Guide | iC2-Micro Frequency Converters
Parameter
number:
1427 Unit: V
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Trip Disable the protection filters and trip at the 1st fault.
1 Warning Run the protection filters normally.
P 2.3.16 Function at Inverter Overload
When the frequency converter issues an inverter overload warning, select whether to continue and probably trip the frequency
converter or derate the output current.
Default value: 0 [Trip] Parameter type: Selection
Parameter
number:
1461 Unit: –
Data type: enum Access type: Read/Write
Selection number Selection name
0 Trip
1 Derate
P 2.3.17 Adjustable Temperature Warning
This parameter is used to warn about the heat sink temperature is high, that is, high ambient temperature or higher load. A trip could
happen if the condition is not rectified. When P 2.1.9 Heat Sink Temperatureplus the value set in the parameter exceed the maximum
value, HEATSINK_CLEAN_WARNING - bit 29 is set in P 5.1.10 Ext. Status Word. The control panel warning indicator light is not turned on
when the specified limit of the parameter is reached.
Default value: Size Related Parameter type: Range (Size Related)
Parameter
number:
442 Unit: –
Data type: uint8 Access type: Read/Write
7.3.3 Modulation (Menu Index 2.4)
P 2.4.2 Min. Switching Frequency
Set the lowest switching frequency allowed by the application.
Default value: 2 [2.0 KHz] Parameter type: Selection
Parameter
number:
1463 Unit: –