Data type: uint16 Access type: Read/Write
P 2.3.10 Fast Mains Phase Loss Min. Power
Fast detection is not activated if the actual power is lower than the value specified in the parameter.
Default value: 10 Parameter type: Range (0–100)
Parameter
number:
1418 Unit: %
Data type: uint16 Access type: Read/Write
P 2.3.13 Auto DC Braking
Protective function against overvoltage at coast in IT grid environment. This parameter is active only when [1] On is selected in this
parameter, and IT grid options are selected in P 1.2.2 Grid Type.
Default value: 1 [On] Parameter type: Selection
Parameter
number:
7 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 Off The function is not active.
1 On The function is active.
P 2.3.14 Max Output Frequency
Enter the maximum output frequency value. P 2.3.14 Max Output Frequency specifies the absolute limit on the frequency converter
output frequency for improved safety in applications where accidental over-speeding must be avoided. This absolute limit applies to all
configurations and is independent of the setting in P 5.4.2 Configuration Mode.
Default value: Size Related Parameter type: Range (0–500)
Parameter
number:
419 Unit: Hz
Data type: uint16 Access type: Read/Write
NOTICE
The parameter cannot be adjusted while the motor is running. Maximum output frequency cannot exceed 10% of the inverter
switching frequency in P 2.4.3 Switching Frequency.
P 2.3.15 Action at Inverter Fault
Select how the frequency converter reacts when an overvoltage, overcurrent, short circuit, or grounding fault occurs.
Default value: 1 [Warning] Parameter type: Selection