Table 61: Overview on data type (continued)
Data type Description Type Range
uint Unsigned integer 8, 16, 32 0 up to 65535
visStr Visible string All strings
7.1.3 Understanding Access Types
Following are the access type of parameters and descriptions.
Table 62: Access Types and Descriptions
Access type Descriptions
Read/Write The setting of the parameter is readable or changeable.
Read The parameter information is only readable.
7.2 Grid (Menu Index 1)
7.2.1 Grid Settings (Menu Index 1.2)
P 1.2.1 Regional Settings
Use the parameter to configure regional settings. Select [0] International to set P 4.2.2.4 Nominal Frequency to 50 Hz. Select [1] North
America to set P 4.2.2.4 Nominal Frequency to 60 Hz.
Default value: 0 [International] Parameter type: Selection
Parameter
number:
3 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
Selection number Selection name Selection description
0 International Default value of P 4.2.2.4 Nominal Frequency is set to 50 Hz.
1 North America Default value of P 4.2.2.4 Nominal Frequency is set to 60 Hz.
P 1.2.2 Grid Type
Select the supply voltage, frequency, and type.
Default value: 12 [380-440V/50Hz] Parameter type: Selection
Parameter
number:
6 Unit: –
Data type: enum Access type: Read/Write
The following are the selections for the parameter.
106 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters