Parameter
number:
713 Unit: s
Data type: uint16 Access type: Read/Write
P 5.10.6 Trip Delay at Torque Limit
Use this parameter to define the delay for tripping the torque warning. When the output torque reaches the torque limit, a warning is
triggered. If the torque limit warning is continuously present for the period specified in this parameter, the frequency converter trips. To
disable the feature, enter the value of 60 s.
Default value: 60 Parameter type: Range (0–60)
Parameter
number:
1425 Unit: s
Data type: uint8 Access type: Read/Write
7.6.10 Mechanical Brake Control (Menu Index 5.11)
P 5.11.1 Brake Closing Speed
Use this parameter to set the motor frequency when the mechanical brake activates, when a stop condition is present.
Default value: 0.0 Parameter type: Range (0.0–400.0)
Parameter
number:
222 Unit: Hz
Data type: uint16 Access type: Read/Write
P 5.11.2 Brake Close Time
Use this parameter to enter the brake delay time for the coast after ramp-down time. The shaft is held at zero speed with full holding
torque. Ensure that the mechanical brake has locked the load before the motor enters coast mode.
Default value: 0.0 Parameter type: Range (0.0–5.0)
Parameter
number:
223 Unit: s
Data type: uint8 Access type: Read/Write
P 5.11.3 Release Brake Current
Use this parameter to set the motor current for release of the mechanical brake, when a start condition is present. The upper limit is
specified with P 2.1.5 Inv. Max. Current.
Default value: 0.00 Parameter type: Range (0.00–100.00)
Parameter
number:
220 Unit: A
Data type: uint32 Access type: Read/Write
176 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters