Application Guide | iC2-Micro Frequency Converters
NOTICE
When mechanical brake control output is selected, but no mechanical brake is connected, the function does not work by default
setting due to too low motor current.
P 5.11.4 Mech. Brake w/ dir. Change
Use this parameter to select whether to use the mechanical brake in direction changes. Select [1] On if the mechanical brake must
engage when the shaft changes direction. The speed at which the mechanical brake engages is selected in P 5.11.1 Brake Closing Speed.
Default value: 0 [Off] Parameter type: Selection
Parameter
number:
239 Unit: –
Data type: enum Access type: Read/Write
The following are the selections of the parameter:
Selection number Selection name
0 Off
1 On
2 On with start delay
7.6.11 Process Control (Menu Index 5.12)
7.6.11.1 Status (Menu Index 5.12.1)
P 5.12.1.1 Process PID Error
This parameter shows the error value in the process PID controller.
Default value: 0.0 Parameter type: Range (-200.0–200.0)
Parameter
number:
1890 Unit: %
Data type: int16 Access type: Read
P 5.12.1.2 Process PID Output
This parameter shows the raw output value from the process PID controller.
Default value: 0.0 Parameter type: Range (-200.0–200.0)
Parameter
number:
1891 Unit: %
Data type: int16 Access type: Read
P 5.12.1.3 Process PID Clamped Output
This parameter shows the output value from the process PID controller after reaching a clamp limit.
Default value: 0.0 Parameter type: Range (-200.0–200.0)
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 | 177