EasyManuals Logo
Home>Danfoss>Media Converter>iC2

Danfoss iC2 User Manual

Danfoss iC2
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #252 background imageLoading...
Page #252 background image
Parameter
Number
617 Unit: V
Data type: uint16 Access type: Read/Write
P 9.5.2.10 T33 Current Dead Zone Scale
A non-zero value for the parameter enables the dead-zone function. The dead-zone band defines an area which could freeze the pointed
speed reference by scaled analog input signal, or ignore unexpected vibration at desired speed caused by disturbance of reference
signal. The bandwidth of dead zone is the double value of P 9.5.2.10 T33 Current Dead Zone Scale.
Default value: 0 Parameter type: Range (0–1000)
Parameter
Number
618 Unit: mA
Data type: uint16 Access type: Read/Write
Dead-zone function
l A non-zero value for the parameter Voltage/Current Dead Zone Scale enables the dead-zone function. The dead-zone band defines
an area which could freeze the pointed speed reference by scaled analog input signal, or ignore unexpected vibration at desired
speed caused by disturbance of reference signal.
l The bandwidth of dead zone is the double value of Voltage/Current Dead Zone Scale.
l Dead-zone band central point is the mid-value of High and Low value of the voltage or current.
l When Low Ref./feedb. Value is a negative value, and the parameter of AI minimum valueLow Voltage/Current set as 0, if the analog
input signal is lost (AI input value = 0), the motor runs at the value of Low Ref./feedb. Value without expectation. This would cause
uncertainty risk or danger. Therefore, the parameters of AI Low Voltage/Current should be set as a non-zero value, like 2 V or 4 mA.
l The following illustration is an example of using T33 analog input (voltage mode, from 2 V to 10 V) for dead-zone function to control
motor running between the speed from -50 Hz to 50 Hz.
e30bv140.10
AI
Reference
P 9.5.2.9 Voltage dead zone scale
(example value: 0.5 V)
Dead zone central point
(example value: 6 V)
(example value: 2 V)
P 9.5.2.2 T33 high voltage
(example value: 10 V)
P 9.5.2.7 T33 low ref./feedb. value
(example value: -50 Hz)
P 9.5.2.9 T33 high ref. /feedb. value
(example value: 50 Hz)
P 9.5.2.3 T33 low voltage
(example value: 2 V)
0 V
0 Hz
Dead zone band
Reverse
Forward
Figure 86: Dead-zone Function Example
The typcial parameter settings for the examples are shown in the following tables.
252 | Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss iC2 and is the answer not in the manual?

Danfoss iC2 Specifications

General IconGeneral
BrandDanfoss
ModeliC2
CategoryMedia Converter
LanguageEnglish

Related product manuals