Parameter
number:
621 Unit: V
Data type: uint16 Access type: Read/Write
P 9.5.3.3 T34 Low Voltage
Enter the voltage (V) that corresponds to the low reference value (set in P 9.5.3.7 T34 Low Ref./Feedb. Value). The value must be set at
>1 V in order to activate the live zero timeout function in P 9.5.6.2 Live Zero Timeout Function.
Default value: 0.07 Parameter type: Range (0.00–10.00)
Parameter
number:
620 Unit: V
Data type: uint16 Access type: Read/Write
P 9.5.3.4 T34 High Current
Enter the current (mA) that corresponds to the high reference value (set in P 9.5.3.6 T34 High Ref./Feedb. Value).
Default value: 20.00 Parameter type: Range (0.00–20.00)
Parameter
number:
623 Unit: mA
Data type: uint16 Access type: Read/Write
P 9.5.3.5 T34 Low Current
Enter the current (mA) that corresponds to the low reference value, set in P 9.5.3.7 T34 Low Ref./Feedb. Value. The value must be set at
>2 mA in order to activate the Live Zero Timeout function in P 9.5.6.2 Live Zero Timeout Function.
Default value: 4.00 Parameter type: Range (0.00–20.00)
Parameter
number:
622 Unit: mA
Data type: uint16 Access type: Read/Write
P 9.5.3.6 T34 High Ref./Feedb. Value
Enter the reference or feedback value that corresponds to the voltage or current set in P 9.5.3.2 T34 High Voltage or P 9.5.3.4 T34 High
Current.
Default value: Size Related Parameter number: Range (-4999.000–4999.000)
Parameter
number:
625 Unit: –
Data type: int 32 Access type: Read/Write
P 9.5.3.7 T34 Low Ref./Feedb. Value
Enter the reference or feedback value that corresponds to the voltage or current set in parameter P 9.5.3.3 T34 High Voltage or P 9.5.3.5
T34 High Current.
Default value: 0 Parameter number: Range (-4999.000–4999.000)