15.2 TROUBLESHOOTING – TYPICAL FAULTS
Symptom
PVED-CLS
operational status
Cause/solution
No actuation (neither
by AUX-steering and
auto-guidance-
steering)
Operational
1. No or insufficient pressure is supplied to the valve.
2. No Auto-guidance controller or AUX-steering device is mapped
3. Flow/angle limited parameters set to ~0
4. No or incorrect auto-steering message from external set-point controller
5. System is in road mode
Fault
1.
Any missing or incorrect input signal/message + wrong parameterization from steering
sensors/switches at the AD1, AD2, AD3 or CAN interface.
2. Insufficient electrical power supply to the PVED-CLS
3. Connector or wiring harness problem
4. Missing wheel angle- or valve calibration
No status available
1. CAN bus not operational. Check connection.
2. No electric power supply
3. Check CAN message addresses
4. PVED-CLS is damaged. (see 5.2)
Opposite actuation
Operational
1. Hoses between valve and steering actuator are swapped
2. Parameter; Invert Flow Direction; (P3080), is set to 255 and PVED-CLS is mounted on
a OSPE/EHi or P3080 is set to 0 and PVED-CLS is mounted on a EHPS
Slow actuation
responds (delays)
Operational
1. Air is trapped in the steering actuator or hoses.
2. Oil has high viscosity. Make sure to apply to the technical requirements listed in the
Danfoss document OSPE Steering valve, SASA sensor, Technical information
3. The requested pressure is supplied with some delay (Pump).
Snake-movement or
shaky-movement in
auto-guidance mode
Operational
1. Shaky-movement: The Open loop dead-band parameters P1 and/or P2 (P1: P3166
+ P3170; P2: P3168 + P3170) is set too aggressive (in flow range) or the Closed
loop dead-band edge, Left/Right (P3166 and P3168) are set too conservative
(inside hydraulic dead-band)
2. Snake-movement: The Open loop dead-band parameters P1 and/or P2 (P1: P3166
+ P3170; P2: P3168 + P3170) is set too conservative (inside hydraulic dead-band)
or the Closed loop dead-band edge, Left/Right (P3166 and P3168) are set too
aggressive (in flow range)
Actuation with low
gain (less flow than
expected)
Operational
1. The offset dead-band CL parameter (P3170) is set too low (inside dead-band) or the
left/right dead-band OL parameters (P3166 and P3168) are set too low (inside dead-
band).
2. The parameters for setting up a steering wheel program (P3522 to P3561) are set too
high
3. Parameter; OSP displacement (P3084) is set greater than the true displacement of the
OSP
4. Parameter Valve capacity (P3088) is set greater than the true flow capacity of the valve
5. Parameters Max Spool Position Let/Right (P3162/P3164) is set too low
6. The soft-stop functionality limits the flow due to wrong settings (P3564 and P3566)
Fault
1. The hydraulic back-up system is active. The steering sensitivity is determined by the
OSP.
PVED-CLS does not
enter normal
operation and stays in
bootloader after
software download
Fault
1. Wrong software downloaded to one of the microcontrollers inside PVED-CLS. Make
sure the correct software is downloaded to the correct controller
Table 61

Table of Contents

Other manuals for Danfoss PVED-CLS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss PVED-CLS and is the answer not in the manual?

Danfoss PVED-CLS Specifications

General IconGeneral
BrandDanfoss
ModelPVED-CLS
CategoryController
LanguageEnglish

Related product manuals