© Danfoss | August 2018 AQ00000211 | 149
17.4.1 Hydraulic config
Name
Description of parameter
Range
Safety critical
parameters ‘S’
Cut-off valve present P3072 U8 -
Cut-off Valve Present/Not Present
Valid Values: 0 (NOT PRESENT); 255 (PRESENT)
OEM 0 255 255 S
Cut-off valve control
mode
P3073 U8 -
Cut-off Valve control mode Close loop Control or ON-OFF control
Valid Values: 0 (ON-OFF control); 255 (Closed loop control)
OEM 0 255 255 S
Cut-off valve CL pull
current
P3074 U16 mAmp Current required to activate Cut-off valve OEM 100 2000 1100 S
Cut-off valve CL hold
current
P3076 U16 mAmp Current required to maintain to Cut-off in ON state OEM 100 2000 500 S
monitoring POST
P3078 U16 x10mSec
Cut Off Valve Activation Timeout for COV Monitoring feature while
entering Off Road state.
INFO: Setting this parameter to 0 will bypass off-road safety check
OEM 0 1000 900 S
Invert flow direction P3080 U8 -
Changes the direction of the requested flow
Valid Values: 0 (NO, DEFAULT OSPE/EHi); 255 (YES, DEFAULT
OEM 0 255 0 S
Valve type P3081 U8 -
Valve type on which the PVED-CLS is mounted
Valid Values: 0 (OSPE, EHi-E); 1 (EHPS); 2 (EHi-H)
OEM 0 2 0 S
Turns lock-to-lock
EHPS
P3082 U16 -
Number of steering wheel turns lock-to-lock, without PVED-CLS activated
(hence pure hydraulic). Lock-to-lock is dependent on:
• OSP displacement
• EH-spool and pilot flow
• Standby pressure (spring force)
• Cylinder volume
Contact your local technical support at Danfoss Power Solutions for
specific calculation, or simply do the measurement/exercise on the vehicle
OEM 100 1000 450 S
OSP displacement P3084 U16 Ccm
OSP displacement, number of cubic centimeters per revolution
Note: When the PVED-CLS is mounted on an EHPS this parameter
OEM 0 1200 120 S
Cylinder stroke volume P3086 U16 Ccm
Acceptable values: 100-10000.
Note: Writing values >10000 will force to use automatic adjusted
cylinder stroke volume-value on WAS calibration
OEM 100 65535 500 S
Valve capacity P3088 U8 Lpm EH valve size, defined in liters per minute OEM 5 120 20 S
compensation
P3089 U8 -
LVDT Offset compensation Enable/Disable
Valid Values: 0 (DISABLE); 255 (ENABLE)
OEM 0 255 255
Absolute spool neutral
threshold range
P3090 U8
Absolute value of Spool neutral threshold range OEM 0 200 25
Max spool pos left copy P3091 S16 x10um
Spool left most position copied by spool auto-calibration before the internal
calculation of the sector CRC
OEM -1000 0 0
P3093 S16
Spool right most position copied by spool auto-calibration before the
internal calculation of the sector CRC
OEM 0 1000 0
P3095 S16
Spool open loop dead-band offset copied by spool auto-calibration before
the internal calculation of the sector CRC
OEM 0 150 0
Cut-off valve PWM pre-
load value
P3097 U8 % Cut-off valve PWM pre-load value OEM 0 100 100
Safety checks IMD -
Rise time limit
P3098 U8 x10mSec
Maximum rise time after switching ON cut-off valve for indicating EH-
Spool is under control during safety check.
OEM 10 100 30 S
Safety checks IMD -
Fall time limit
P3099 U8 x10mSec
Maximum fall time after switching OFF cut-off valve for indicating EH-
Spool is under control during safety check
OEM 10 100 25 S
Safety checks IMD -
Pass criteria
P3100 U8 dec
P3100 specifies how many safety check cycles with successful EH-Spool
control shall be executed before PVED-CLS passes the safety checks.
OEM 2 8 2 S
Safety checks IMD -
Maximum fall time
P3101 U16 x10mSec
If the EH-Spool does not return to neutral within this timeout, the cut-off
solenoid is concluded to be stuck open.
OEM 100 1000 100
Table 64