FC 300 Design Guide
How to Program
" Parameters: Load and Motor
" 1-0* General Settings
1-00 Configuration Mode
Option:
*
Speed open loop [0]
Speed closed-loop [1]
Torque [2]
Function:
Speed control, open loop: Enables speed control
(without fe edback sig n al from motor) with automatic
slip compensation for almost constant s peed at
varying loads. Compensations are active, but can
be disabled in the Load / Motor parameter group.
Speed control, closed loop: Enables encoder
feedback from motor. Obtain full holding torque
at 0 RPM. Increased spe ed accuracy: Provide a
feedback signal and set the spe ed PID controller.
Torque control, speed feedback: Connect the
encoder speed feedback signal to the encoder input.
Only possib le with "Flux wit h encoder
feedback", par. 1-01.
1-01 Motor Control Principle
Option:
U/f [0]
VVC
plus
[1]
Flux sensorless [2]
Flux w/ motor feedback [3]
Function:
Determines which m otor control princ iple to e mploy.
[0] U/f is spec ial m otor mode. Used for specia l
motor applications as parallel connected motors.
Generally, the best shaft performance is obtained
in the two Flux Vector control m ode s Flux w/
encoder feedback [3] and Flux sensorless [2]. Most
applications, however, are easily handled u sing a
Voltage Vector control mode VVC
plus
[1]. T
he main
benefit of VVC
plus
operation is a simpler motor model.
Par. 1-01 cannot be adjusted while the
motor is running.
1-02 Flux Motor Feedback Source
Option:
*
24 V encoder [1]
MCB 102 [2]
Function:
24 V encoder [1] is an A and B channel encoder.
The encoder can be connected to the digital
inputs terminals 32/33 only.
MCB 102 [2] is selection of encoder module.
Par. 1-02 cannot be adjusted while the
motor is running.
1-03 Torque Characteristics
Option:
*
Constant torque [0]
Variable torque [1]
Auto Energy Optim. [2]
Function:
Select the demanded torque characteristic. AEO and
VT are different kinds of energy-saving operation.
Constant torque [0]: The motor shaft output will
provide constant torque by variable speed control.
Variable Torque [1]: The motor shaft output will
provide a variable torque by variable speed control.
Setvariabletorquelevelinpar. 14-40.
Automatic Energy Optimizing function [2 ]:
Automatically adjusts the optimize d energy
consumption by setting par. 14-41 and par. 14-42
1-05 Local Mode Configuration
Option:
Speed o pen-loop [0]
Speed closed-loop [1]
*
As conf. mode P. 1-00 [2]
Function:
Select w h ich application configuration mode (par.
1-00) to use when a Local (LCP) Reference is
active. A Local Reference can only be active if
par. 3-13 is [0] or [2]. By default the L ocal
Reference i s only active in Hand Mode.
" 1-1*
1-10 Motor Construction
Option:
*
Asynchron [0]
PM, non salient SPM [1]
Function:
Motor construction can either b
e asynchronous
or permanent magnet (PM) motor.
*
default setting ()display text []value for use in communication via serial communication port
140
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals