FC 300 Design Guide
How to Select Your VLT
" Ordering Numbers: LC Filter Modules,
380-500 VAC
Mains supply 3 x 380 - 500 V
FC 301/ FC 302
LC filter
enclosure
Rated current at
400/500 V
Max. torque
at CT/VT
Max. output
frequency
Ordering
no.
PK37-P3K0 Bookstyle IP 20 7.2 A / 6.3 A 160% 120 Hz 175Z0825
P4K0-P7K5 Bookstyle IP 20 16 A / 14.5 A 160% 120 Hz 175Z0826
PK37-P7K5
Compact IP 20 16 A / 14.5 A 160% 120 Hz 175Z0832
LC filters for FC 300, 525 - 600 V, please contact Danfoss.
NOTE
When using LC filters, the switching frequency must be minimum
4.5 kHz (see par. 14-01).
" Electrical Data
" Mains Supply 3 x 200 - 240 VAC
FC 301/FC 302
Typica l Sh aft Output [HP, kW]
0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 3.7 4 5.5 7.5
Output current
Continuous
(3 x 200-240 V) [A]
1.8 2.4 3.5 4.6 6.6 7.5 10.6 12.5 16.7 - - -
Intermittent
(3 x 200-240 V) [A]
2.9 3.8 5.6 7.4 10.6 12.0 17.0 20.0 26.7 - - -
Continuous
KVA (208 V AC) [KVA]
0.65 0.86 1.26 1.66 2.38 2.70 3.82 4.50 6.00 - - -
Max. cable size
(mains, motor, brake)
[AWG]
2
,[mm
2
]
24 - 10 AWG
(0.2 - 4 mm
2
)
---
Max. input current
Continuous
(3 x 200-240 V) [A]
1.62.23.24.15.96.89.511.315.0- - -
Intermittent
(3 x 200-240 V) [A]
2.6 3.5 5.1 6.6 9.4 10.9 15.2 18.1 24.0 - - -
Max. pre-fuses
1
[A] 101010102020203232---
Environment
Estimated power loss
at rated max. load [HP, kW]
58 66 79 94 119 147 178 228 274 - - -
Enclosure IP 20
Weight, enclosure IP2 0 [lb,
kg]
4.74.74.84.84.94.94.96.66.6- - -
Efficiency 0.95 0.95 0.95 0.95 0.96 0.96 0.96 0.96 0.96 - - -
74