FC 300 Design Guide
How to Program
" Status Wo rd According to FC Profile (S TW )
The status word informs the maste r (e.g. a PC) of the
slave (adjustable frequency dr ive) operation mode.
Slave = > master
1 2 3 ..... 10
STW MAV PCD ..... PCD
PCD read/write
Explanation of the Status Bits
Bit Bit value = 0 Bit value = 1
00 Control not ready Control ready
01 Drive not ready Drive ready
02 Coasting Enable
03 No error Trip
04 No error Error (no trip)
05 Reserved -
06 No error Triplock
07 No warning Warning
08 Spee d ≠ referen ce Speed = reference
09 Local operation Bus control
10 Out of frequency limit Frequency limit OK
11 No operation In operation
12 Drive OK Stopped, a utostart
13 Voltage OK Voltage exceeded
14 Torque OK Tor q ue e xceeded
15 Timer OK Timer e xceeded
Bit 00, Control not ready/ready:
Bit 00 = "0": The adjustable frequency drive trips. Bit 00 = "1": The adju
stable frequency
drive controls are ready but the power component does not necessarily receive any power
supply (in case of external 24 V supply to controls).
B
it 01, Drive ready:
Bit 01 = "1": The adjustable frequency drive is ready for opera
tion but the coasting comma nd
is active via the digital inputs or via serial communication.
B
it 02, Coasting stop:
Bit02="0": Theadjustablefrequencydrivereleases the motor. Bit 02 = "1": The adjustable
frequency drive starts the motor with a start command.
B
it 03, No error/trip:
Bit 03 = "0" : The adjustable frequency drive is not in fault mode. Bit 03 = "1": The adjustable
frequency drive trips. To re-establish o peration, enter [Reset].
B
it 04, No error/e rror (no trip):
Bit 04 = "0": The adjustable fre quency drive is not
infaultmode. Bit04="1": The
adjustable frequency drive shows an error but does not trip.
*
default setting ()display text []value for use in communication via serial c ommunication port
246
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals