FC 300 Design Guide
How to Program
Bit 05, Not used:
Bit 05 is not use d in the status word .
B
it 06, No error / triplock:
Bit 06 = "0": The adjustable frequency drive is not in fault m ode. Bit 06 = "1": The
adjustable frequency drive is tripped and locked.
B
it 07, No warning/warning:
Bit 07 = "0": The re are no warnings. Bit 07 = "1": A warning has occurred.
B
it 08, Sp eed≠reference/speed = reference:
Bit 08 = "0": The motor is running but the present speed is different from the preset speed
reference. This might be the case e.g. when the speed ramps up/down during start/stop. Bit
08 = "1": The motor speed matches the preset speed reference.
B
it 09, Local operation/bus cont rol:
Bit 09 = "0": [STOP/RESET] is act ivate on the control unit or Local control in par. 3-13 Reference site is
selected. You cannot control the adjustable frequency drive via serial communicat
ion. Bit09="1": Itis
possible to control the adjustable frequency d rive via the field bus/ serial com munication.
B
it 10, Out of frequency limit:
Bit 1 0 = "0": The output frequency has reached the value in par. 4-11 M otor speed low limit or par.
4-13 Motor speed high limit. Bit 10 = "1": T he output frequency is within the define
d limits.
B
it 11, No operation/in op e ration:
Bit 11 = "0": The m otor is not running. Bit 11 = "1": The adjustable frequency drive has
a start signal or the output frequency is greater than 0 Hz.
B
it 12, Drive OK/stopped, autostart:
Bit 12 = "0": There is no temporary overheating in the inverter. Bit 12 = "
1": The inverter stops because of
overheating but the unit does not trip and will resume operation once t he overheating stops.
B
it 13, Voltage OK/limit exceeded:
Bit13="0": Therearenovoltagewarnings. Bit13="1": TheDCvoltageintheadjustable
frequency drive’s intermediate circuit is too low or too hig
h.
B
it 14, Torque OK/limit exceeded:
Bit 14 = "0": The m otor current is lower than the torque limit selected in par. 4-18 Current Limit.
Bit 14 = "1": The torque limit in par. 4-18 Current Limit is exceeded.
B
it 15, Timer OK/limit exceeded:
Bit 15 = "0": The timers for motor thermal protection an
d VLT thermal protection are not
exceeded 100%. Bit 15 = "1": One of the timers exceeds 100%.
*
default setting ()display text []value for use in communication via serial c ommunication port
247
MG.33.B
3.22 - VLT is a registered Danfoss trademark