FC 300 Design Guide
How to Program
" Parameters: Communications
and Options
" 8-0* General Settings
8-01 Control Site
Option:
*
Digital and ctrl. word [2] [0]
Digital only [1]
Control word only [2]
Function:
Specifies the control as either Digital inputs ,
Control word,orboth. Thisparameteroverrules
the settings in par. 8-50 to 8-56.
8-02 Control W ord Source
Option:
*
FC RS-485 [0]
FC USB [1]
Option A [2]
Function:
Specifies the source of the control word, serial
interface, or installed option. During initial
power-up, the adjustable frequency drive
automatically s ets this parameter to Option A if it
detects if a valid bus option installed in this slot. If
the option is removed, the adjustable frequency
drive detects a change in the configuration and
sets par. 8-02 back to default setting FC RS-485.
The adjustable frequency drive trips. If an option
is installed after initial power-up, the setting of
par. 8-02 does not change but the drive will trip
and display: Alarm 67 Option Change.
8-03 Control Word Timeout Time
Range:
0.1 - 18000.0 s
*
1.0s
Function:
Sets the maximum time expected to pass between
the reception of two consecutive telegrams. If
this time is exceeded, it indic ates that serial
communication has stopped. T he function selected
in p a r. 8-0 4 will then be carried out.
8-04 Control Word Timeout Function
Option:
*
Off [0]
Freeze Out put [1]
Stop [2]
Jogging [3]
Max. Speed [4]
Stop and trip [5]
Select set-up 1 [7]
Select set-up 2 [8]
Select set-up 3 [9]
Select set-up 4 [10]
Function:
A valid control word triggers the timeout counter.
Acyclic DP V1 does not trigger the timeout counter.
The time-out function is activated if the control
word is not updated w ithin the time specified in
par. 8-03 Control Word Time-out Time.
- Off: Control via serial bus (Fieldbus or standard)
resumes and us es the most recent control word .
- Freeze output frequency: Freeze output
frequency until communication resumes.
- Stop with auto restart: Stop with auto restar t
when communication resumes.
- Output frequency = JOG freq.: The motor runs
at JOG frequency until communication resumes.
- Output frequency = Max. freq.: The
motor runs at maximum frequency until
communication resumes.
- Stop w ith trip: The motor stops. Reset
the adjustable frequency drive, see
explanation above.
Select set-up x:
This type of timeout function is u sed for changing
set-up on a control word timeout. If communication
resumes caus ing the time out situation to disappear,
par. 8-05 End-of-time-out Function defines
whether
to resume the set-up used before the time-out or to
hold the set-up endorsed by the time-out function.
Note that the follow ing parameters have to be
configured for the set-up change to o
ccur on a
timeout. Par. 0-10 Active set-up has to be set
to Multi set-up alo ng with the relevant linking
set in par. 0-12 This Set-up Linked
To.
8-05 End-of-Timeout Function
Option:
*
Hold set-up [0]
Resume set-up [1]
*
default setting ()display text []value for use in communication via serial communication port
182
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals