FC 300 Design Guide
How to Program
" Parameters: Analog In/Out
" 6-0* Analog I/O Mode
FC 300 is equipped w ith 2 analog inputs: Terminal
53 and 54. The analog inputs on FC 302 are
designed for free selection of either voltage (-10V
- +10V) or current input (0/4 - 20 mA).
NOTE
Thermistors are connected either to an
analog or a digital input.
6-00 Live Zero Time out Time
Range:
1-99s
*
10s
Function:
Is active when A53 (SW201) and /or A5 4 (SW202)
is/are in the position ON (the analog inputs are
selected to current input s). If the reference signal
value connected to the selected current input falls
below 50% of the value set in par. 6-12 or par. 6-2 2
for a period longer than the time set in par. 6-00,
the function se lected in p ar. 6-01 is activated.
6-01 Live Zero Timeout Function
Option:
*
Off [0]
Freeze Out put [1]
Stop [2]
Jogging [3]
Max. speed [4]
Stop and trip [5]
Function:
Activates the function if the input signal on term inal
53 or 54 drops below 2 mA, provided that par.
6-12 or 6.22 is set higher than 2 mA, and that
the time for time out in par. 6-0 0 is exceeded.
If more timeouts occur at the same time, the
adjustable frequency drive makes t
he following
priority of the time-out function:
1. Live Zero Time-out Function par. 6-01
2. Encoder Loss Function par. 5-74
3. Control-word Time-out Function par. 8-04.
The output frequency of the adjustable
frequency drive can be:
• frozen at the present value
• overruled to jog speed
• overruled to max. speed
• overruled to stop with subsequent trip
• overruled to Set-up 8.
It i s not possib le to se t the parameter
while the motor is running.
" 6-1* Analog Input 1
6-10 Terminal 5 3 Low Voltage
Range:
0.0 - par. 6-11
*
0.0V
Function:
Sets the analog input scaling value to correspond to
the minimum reference value (set in par. 3-02).
6-11 Termin al 53 H igh Volt age
Range:
Par. 6-10 to 10.0 V
*
10.0V
Function:
Sets the analog input scaling value to correspond to
the m aximum reference value (set in par. 3-03).
6-12 Term inal 53 Low Current
Range:
0.0topar. 6-13mA
*
0.0mA
Function:
Determines the value of the reference signal to
correspond to the minimum reference value (set in
par. 3-02). I f the Time-out function o f par. 6-01
is activated, the value must be se t at >2 mA.
6-13 Term inal 53 High Current
Range:
Par. 6-12 to - 20.0 mA
*
20.0 m A
*
default setting ()display text []value for use in communication via serial communication port
175
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals