FC 300 Design Guide
How to Program
Function:
Sets the value of the reference signal to correspond
to the maximum reference value (set in par. 3-03).
6-14 Termin al 53 Low Ref./Feedb. Value
Range:
-100000.000 to par. 6-15
*
0.000 Unit
Function:
Sets the a nalog input scaling t o correspond
to the minimum reference feedback value
(set in par. 3-01).
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Par. 6-14 to 10000 0.000
*
1500.000 Unit
Function:
Sets the ana log input scaling value to correspond
to the m aximum reference feed back value
(set in par. 3-01).
6-16 Terminal 53 Filter Time Cons tant
Range:
0.001 - 10.000 s
*
0.001s
Function:
A 1st order digital low-pass filter time constant
for suppressing electrical noise on terminal
53. It is not possible to set the parameter
while the motor is running.
" 6-2* Analog Input 2
6-20 Termin al 54 Lo w V oltage
Range:
0.0 - par. 6-21
*
0.0V
Function:
Sets the ana log input scaling value to correspond
to the minimum reference value (set in par.
3-02).See also section Reference Handling.
6-21 Termin al 54 High Voltage
Range:
Par. 6-20 to 10.0 V
*
10.0V
Function:
Sets the analog input scaling value t o correspond to
the m aximum reference value (set in par. 3-03).
6-22 Term inal 54 Low Current
Range:
0.0topar. 6-23mA
*
0.0mA
Function:
Determines the value of the reference signal to
correspond to the minimum reference value (set in
par. 3-02). I f the Time-out function o f par. 6-01
is activated, set the value at >2 mA.
6-23 Term inal 54 High Current
Range:
Par. 6-12 to - 20.0 mA
*
20.0 mA
Function:
Sets the value of the reference signal to correspond
to the maximum reference value (set in par. 3-03).
6-24 Term in al 54 Low Ref./Feedb. Value
Range:
-100000.000 to par. 6-25
*
0.000 Unit
Function:
Sets the analog input scaling value to correspond
to the minimum reference feedback value
(set in par. 3-01).
6-25 Terminal 54 high ref./feedb. value
Range:
Par. 6-24 to 1000 00.000
*
1500.000 Unit
Function:
Sets the analog input scaling value to correspond
to the maximum reference feedback value
(set in par. 3-01).
6-26 Terminal 54 Filter Time Constant
Range:
0.001 - 10.000 s
*
0.001s
Function:
A 1st order digital low-pa ss filter time constant
for suppressing electrica l noise on terminal
53. It is not possible to set the parameter
while the motor is running.
" 6-5* Analog Output 1
Analog outputs are current outputs: 0/4 - 20
mA. Common terminal (terminal 39) is the same
*
default setting ()display text []value for use in communication via serial communication port
176
MG.33.B
3.22 - VLT is a registered Danfoss trademark