4 Product overview
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
18
Technical data and other information on the type label
Technical data / information Description
M6A M8A M10A
Model: RPI M6A Model: RPI M8A Model: RPI M10A Delta Model name
P/N: RPI602FA0E1000 P/N: RPI802FA0E1000 P/N: RPI103FA0E1000 Delta Part number
DC Input
200-1000Vdc DC input voltage range
MPPT 315-800Vdc MPPT 415-800Vdc MPPT 415-800Vdc
MPP input voltage range with full power (with symmetrical
load)
1000Vdc 1000Vdc 1000Vdc Maximum DC input voltage
10A/10A max 10A/10A max 15A/10A max Maximum DC input current DC input DC1 / DC2
Total 20A max Total 20A max Total 25A max Total maximum DC current
Voc: 1000VDC max Voc: 1000VDC max Voc: 1000VDC max
Maximum Open circuit voltage
Isc: 13A/13A max Isc: 13A/13A max Isc: 19.5A/13A max
Maximum DC short circuit current x number of
strings
AC Output
220/380, 230/400 Vac 220/380, 230/400 Vac 220/380, 230/400 Vac AC Nominal voltage
50/60 Hz 50/60 Hz 50/60 Hz AC Nominal frequency
6kVA nom 8kVA nom 10kVA nom Nominal reactive power
6.3kVA max
(1) 4.99 kW max for AU/NZ
PL 4.99k
8.4kVA max 10.5kVA max
Maximum reactive power;
The RPI M6A will be limited to 4.99 kW if grid type AU/NZ
PL 4.99k is selected (applies to Australia and New Zea-
land only)
9.7A max 13A max 16A max Maximum AC current
3P3W or 3P4W 3P3W or 3P4W 3P3W or 3P4W
The inverter can be connected to a 3-phase-grid with a
3-wire system (3 phases + PE) or with a 4-wire system (3
phases + N + PE)
cosφ 0.8ind~0.8cap cosφ 0.8ind~0.8cap cosφ 0.8ind~0.8cap Range of cos φ
Standards and directives
VDE 0126-1-1/A1 VDE 0126-1-1/A1 VDE 0126-1-1/A1
The inverter fulls the requirements of standard VDE 0126-
1-1/A1.
VDE-AR-N 4105 VDE-AR-N 4105 VDE-AR-N 4105
The inverter fulls the requirements of standard VDE-AR-N
4105.
CE marking. With the marking Delta declares that the
inverter meets the requirements of the applicable EC direc-
tives.
Environmental information
Safety Class: 1 Safety Class: 1 Safety Class: 1 Safety class according to EN 61140
OVC: III OVC: III OVC: III Overvoltage category according to IEC 62109-1
Ambient temp:
-25°C...+60°C
Ambient temp:
-25°C...+60°C
Ambient temp:
-25°C...+60°C
Operating temperature range
IP65 IP65 IP65 Protection degree according to EN 60529