EasyManuals Logo
Home>Delta>Inverter>RPI M6A

Delta RPI M6A User Manual

Delta RPI M6A
116 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
8 Settings
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
94
8.18 Constant Q
Overview
With this function you can set a constant reactive power.
This function should be set only when requested by country regulations, authorities or your grid operator.
Accessing the menu
Main menu > Active/Reactive Pwr > Active Power Ctrl > Constant Q
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the main menu. Oth-
erwise, repeatedly press the button
ESC
until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2. Use the buttons and to select Active/Reactive Pwr.
To conrm your selection, press the button
ENT
.
Password: * * * *
energy production
Adj. would effect
Warning:
3. The menu is protected by password 5555. Use the buttons and to set each digit.
To conrm a digit, press the button
ENT
.
Reactive Power Ctrl
Active Power Ctrl
4. Use the buttons and to select Reactive Power Ctrl. The current setting is
displayed behind the menu entry.
Q(V)
Constant Q
Cos phi (P)
Constant cos phi
5. Use the buttons and to select Constant Q. The current setting is displayed
behind the menu entry.
Do not change this setting without prior
consultation with Delta Solar Support.

Table of Contents

Other manuals for Delta RPI M6A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI M6A and is the answer not in the manual?

Delta RPI M6A Specifications

General IconGeneral
BrandDelta
ModelRPI M6A
CategoryInverter
LanguageEnglish

Related product manuals