8.8.5 P Ramp Up
Overview
With this function you can dene a ramp for the active power in case the inverter has disconnected from the grid because of a grid volt-
age or grid frequency failure (see “8.8.2 Voltage protection”, p. 73 and “8.8.3 Frequency protection”, p. 76). After the failure has
disappeared, the inverter will continuously increase the active power fed into the grid according to the set ramp.
Accessing the menu
Main menu > Install Settings > Grid settings > P Ramp Up
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the main menu. Oth-
erwise, repeatedly press the button
ESC
until the main menu is displayed.
General Settings
Install Settings
2. Use the buttons and to select Install Settings.
To conrm your selection, press the button
ENT
.
energy production
Adj. would effect
3. Type in the password you received from Delta Support. Use the buttons and to
set each digit.
To conrm a digit, press the button
ENT
.
4. Use the buttons and to select Grid settings.
To conrm your selection, press the button
ENT
.
Freq. Protection
Reconnect T: 60s
P Ramp up: 10%/m
Voltage Protection
5. Use the buttons and to select P Ramp Up.
This subsection consists of only one parameter which can be directly edited.
6. To start editing the parameter value, press the button
ENT
.
7. To change the parameter value, use the buttons and .
To conrm your setting, press the button
ENT
.
To cancel the action, press the button
ESC
.
Congurable Parameters
Parameter Description Value range
P Ramp up
After the failure has disappeared, the inverter will continuously
increase the active power fed into the grid according to the set ramp
0 ... 6000 %/min
Do not change this setting without prior
consultation with Delta Solar Support.