81
Installation and Operation Manual for RPI M6A M8A M10A inverters V1.0 2016-02-03
8 Settings
8.10 EPO (External Power Off)
Overview
With this function you can set the type of contact for the EPO function (normally open or normally closed).
Accessing the menu
Main menu > Install Settings > EPO
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the main menu. Oth-
erwise, repeatedly press the button
ESC
until the main menu is displayed.
Inverter Info.
General Settings
2. Use the buttons and to select Install Settings.
To conrm your selection, press the button
ENT
.
energy production
Adj. would effect
3. The menu is protected by password 5555. Use the buttons and to set each digit.
To conrm a digit, press the button
ENT
.
Dry Cont. Disable
RCMU: ON
EPO: Normal Close
4. Use the buttons and to select EPO. The current setting is displayed behind the
menu entry.
5. To start editing the parameter value, press the button
ENT
.
6. To change the parameter value, use the buttons and .
To conrm your selection, press the button
ENT
.
To cancel the action, press the button
ESC
.
Congurable Parameters
Parameter Description Value range
EPO
Sets the type of contact for the relay (normally closed or normally
open).
Normal Open | Normal Close
Default setting: Normal Close