8 Settings
8.20 FRT (Fault Ride Through)
Overview
Values have been set based upon country standards. If you modify these values, you will lose certication.
Therefore you should set this function only when requested by country regulations, authorities or your grid
operator.
With this function you can set the operation behavior of the inverter for FRT (Fault Ride Through).
U
grid
/U
n
V
drop
U
1
U
min
100%
t
0
t
1
t
3
time
Stay connected
Disconnect from grid
Fig. 8.41: Operation behavior for FRT (Fault Ride Through)
t1 : The point in time when the fault occurs.
Accessing the menu
Main menu > FRT
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. When the default information is displayed, press any button to open the main menu. Oth-
erwise, repeatedly press the button
ESC
until the main menu is displayed.
Inverter Info.
General Settings
2. Use the buttons and to select FRT.
To conrm your selection, press the button
ENT
.
energy production
Adj. would effect
Warning:
3. The menu is protected by password 5555. Use the buttons and to set each digit.
To conrm a digit, press the button
ENT
.
Do not change this setting without prior
consultation with Delta Solar Support.